Built-in By-pass Contactor Soft Starter FWI-SSN3 series 5.5KW-75KW

Power arrange: 5.5KW-75KW

Power supply: three-phase AC 380V or 660V±15%, 50 Hz or 60 Hz

1.png

Model

Rated power (KW)

Rated current

(A)

External dimensions

Installation dimensions

Net weight (kg)




HI

W1

D

H2

W2

d


FWI-SSN3-5d5

5.5

11

310

155

175

296

128

M6

≈5

FWI-SSN3-7d5

7.5

15

310

155

176

296

128

M6

≈5

FWI-SSN3-011

11

22

310

155

176

296

128

M6

≈5

FWI-SSN3-015

15

30

310

155

176

296

128

M6

≈5

FWI-SSN3-018

18.5

37

310

155

176

296

128

M6

≈5

FWI-SSN3-022

22

43

310

155

176

296

128

M6

≈5

FWI-SSN3-030

30

60

310

155

176

296

128

M6

≈5

FWI-SSN3-037

37

75

310

155

176

296

128

M6

≈5

FWI-SSN3-045

45

90

310

155

176

296

128

M6

≈5

FWI-SSN3-055

55

110

310

155

176

296

128

M6

≈5

FWI-SSN3-075

75

150

310

155

176

296

128

M6

≈5


Model

Rated power (KW)

Rated current (A)

External dimensions

Installation dimensions

Net weight (kg)




HI

W1

D

H2

W2

d


FWI-SSN3-090

90

160

585

265

240

490

235

M8

≈27

FWI-SSN3-115

115

200

585

265

240

490

235

M8

≈27

FWI-SSN3-132

132

250

585

265

240

490

235

M8

≈27

FWI-SSN3-160

160

300

585

265

240

490

235

M8

≈27

FWI-SSN3-200

200

360

585

265

240

490

235

M8

≈27


Classification

 

Connection point output

Terminal marking

 

01,02

Terminal description

 

Power input

Function description

 

01, 02 are AC220V power input to the control panel


03,04

 

 

05,06

Running output (delay)

 

 

Fault output

03, 04 are programmable relay output, the delay time is set by the code F4 while the output function time is set by code FE.

 

005, 06 are fault relay output, they will be on when there's fault with the soft starter or the power is cut off and be of! when the power is on. (capacity of the connection point AC250V/3A)

Connection point input

07

Instantaneous stop input

rhe motor will stop immediately when 07 and 10 are disconnected (or be tandemly connected to the normally closed point of the thermal relay)


08

Soft stop input

The motor will slow down for soft stop when 08 and 10 are disconnected (or automatically stop).


09

Start input

the motor will start for running when 09 and 10 are connected.


10

Common terminal

Common terminal for signal input of the connection points

Analog output

11,12

Analog output

11 and 12 are 4~20Ma DC analog output which are used to monitor the current of the motor in real time. The maximum value 20mA indicates the current of the motor is four times oi the nominal current of the soft starter.4~20Ma DC meter can be connected for observation. Maximum load resistance this output is 300Q.

Communication

DB

RS485communication input/output

Input and output signal terminal of RS485 communication, can be used to connect several soft starters.