V51-H/V61-H (Synchronous)
V51-H/V61-H (Synchronous) inverter description
1.1 Product Model Description
1.2 Product Nameplate Description
Notice: V51 is sensorless vector control series, V61 is sensor vector control series.
1.3 Product Series
V61−H−4T□□□G & V51−H−4T□□□G Three−phase 400V Constant torque/heavy−duty application
Power (kW) | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | 75 | |
Motor power (kW) | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | 75 | |
Output | Voltage (V) | Three−phase 0 to rated input voltage | ||||||||||||||
Rated current (A) | 2.5 | 3.8 | 5.5 | 9 | 13 | 17 | 24 | 30 | 39 | 45 | 60 | 75 | 91 | 112 | 150 | |
Overload capacity | 150% 1 minute, 180% 10 seconds, 200% 0.5 second, interval: 10 minutes (inverse time lag feature) | |||||||||||||||
Input | Rated voltage/frequency | Three−phase 380V/480V; 50Hz/60Hz | ||||||||||||||
Allowable voltage range | 323V ~ 528V; Voltage unbalancedness ≤3%; allowable frequency fluctuation: ±5% | |||||||||||||||
Rated current (A) | 2.8 | 4.2 | 6.1 | 10 | 15 | 19 | 26 | 33 | 43 | 50 | 66 | 83 | 100 | 123 | 165 | |
Braking unit | Built−in as standard | Built−in as option | ||||||||||||||
Protection class | IP20 | |||||||||||||||
Cooling mode | Self−cooling | Forced air convection cooling | ||||||||||||||
Power (kW) | 90 | 110 | 132 | 160 | 185 | 200 | 220 | 250 | 280 | 315 | 355 | 400 | 450 | 500 | ||
Motor power (kW) | 90 | 110 | 132 | 160 | 185 | 200 | 220 | 250 | 280 | 315 | 355 | 400 | 450 | 500 | ||
Output | Voltage (V) | Three−phase 0 to rated input voltage | ||||||||||||||
Rated current (A) | 176 | 210 | 253 | 304 | 350 | 380 | 426 | 470 | 520 | 600 | 650 | 690 | 775 | 860 | ||
Overload capacity | 150% 1 minute, 180% 10 seconds, 200% 0.5 second, interval: 10 minutes (inverse time lag feature) | |||||||||||||||
Input | Rated voltage/frequency | Three−phase 380V/480V; 50Hz/60Hz | ||||||||||||||
Allowable voltage range | 323V ~ 528V; Voltage unbalancedness ≤3%; allowable frequency fluctuation: ±5% | |||||||||||||||
Rated current (A) | 160* | 196* | 232* | 282* | 326* | 352* | 385* | 437* | 491* | 580* | 624* | 670* | 755* | 840* | ||
Braking unit | External braking unit needed | |||||||||||||||
Protection class | IP20 | |||||||||||||||
Cooling mode | Forced air convection cooling |
*V61−H−4T90G & V51−H−4T90G and above products are equipped with external DC reactor as standard.
1.4 Technical Specifications of Product
Control features | Control mode | Sensorless Vector Synchronous/Asynchronous Control | Sensor Vector Synchronous/Asynchronous Control |
Startup torque | Asynchronous 0.25Hz 200% rated torque Synchronous 2% rpm 150% rated toruqe | 0 rpm 200% rated toruqe | |
Speed adjustment range | 1:200 | 1:5000 | |
Speed stabilization precision | ± 0.5% | ± 0.02% | |
Product functions | Key functions | field weakening control, undervoltage adjustment, switching of AC operation grounding, protective grounding and DC operation grounding, rotation speed tracing, torque limitation, multi−speed operation (up to 23 speeds), auto tuning, S curve acceleration/deceleration, slip compensation, PID adjustment, drooping control, current limiting control, torque control mode and speed control mode switching, manual/auto torque boost. current limiting, multi−functional input/output terminal | |
Frequency setting mode | Operation panel setting, terminal UP/DN setting, host computer communication setting, analog setting AI1/AI2/AI3, terminal pulse DI setting, simple PLC setting | ||
Powered braking capacity | Braking unit action voltage: 650 ~ 750V; operating time: 100.0s; The braking unit can be embedded for V6−H−4T75G and below equipment | ||
DC braking capacity | DC braking initial frequency: 0.00 ~ 300.00Hz; DC braking current: Constant torque: 0.0 ~ 120.0%, Variable torque: 0. 0 ~ 90.0% DC braking time: 0.0 ~ 30.0s; there is no initial waiting time for the DC braking to realize quick braking | ||
Magnetic flux braking function | Ongoing action and no action upon deceleration as option, no action upon deceleration at default | ||
Unique functions | Multifunctional M key | The unique multifunctional key is used to set the frequently used operations: JOG, emergency shutdown, running command reference mode switch , menu switching | |
Multiple menu modes | Basic menu mode, fast menu mode. Menu mode of non−leave−factory value function codes, Menu mode of last changed 10 function codes | ||
Parameter copy | The standard operation panel can realize the parameter upload, download and display the copy progress. The user can select to forbid the overwriting of the uploaded parameters. | ||
Displayed/hidden function code | The customer can select to display or hide the function codes by themselves. | ||
Dual 485 communication ports | Dual 485 communication ports support Modbus protocol (RTU). The standard operation panel can realize remote control box function with a maximum distance of 500m. | ||
Operation panel | Button type or shuttle type operation panel optional, protection class: IP20 as standard, IP54 as option | ||
Common DC bus | The full series can realize common DC bus supply for several inverters. | ||
Independent duct | The full series adopts independent duct design and supports the installation of heatsink outside the cabinet | ||
Universal expansion interface | Universal expansion board equipped with CPU for supporting customers secondary development: physical interface SPI bus, software protocol Modbus | ||
Expansion card | User’s secondary development card, injection molding machine interface card, PG feedback card, air compressor control card, communication adapter card, power monitoring card, phase sequence detection card, external power rectifying card | ||
Power−up auto−detection | Realizing the power−up auto−detection of internal and peripheral circuits, including motor grounding, abnormal +10V power supply output, abnormal analog input, and disconnection | ||
Protection function | Power supply undervoltage, overcurrent protection, overvoltage protection, interference protection, abnormal comparison reference input, auto−tuning failure, module protection, heatsink overtemperature protection, inverter overload protection, motor overload protection, peripheral protection, abnormal current detection, output to ground short circuit, abnormal power failure during operation, abnormal input power, output phase failure, abnormal EEPROM, abnormal relay contact, temperature sampling disconnection, encoder disconnection, abnormal +10V power supply output, abnormal analog input, motor overtemperature (PTC), abnormal communication, abnormal version compatibility, abnormal copying, abnormal expansion card connection, terminal mutual exclusion detection failure, hardware overload protection | ||
Efficiency | At rated power, 7.5kW and below power class ≥93%, 45kW and below power class ≥95%, 55kW and above power class ≥98% | ||
Environment | Operating site | The product shall be mounted vertically in the electric control cabinet with good ventilation. Horizontal or other installation modes are not allowed. The cooling media is the air. The product shall be installed in the environment free from direct sunlight, dust, corrosive gas, combustible gas, oil mist, steam and drip. | |
Ambient temperature | −10 ~ +40ºC, derated at 40 ~ 50ºC, the rated output current shall be decreased by 1% for every temperature rise of 1ºC | ||
Humidity | 5 ~ 95%, no condensing | ||
Altitude | 0 ~ 2000m, derated above 1000m, the rated output current shall be decreased by 1% for every rise of 100m | ||
Vibration | 3.5mm,2~9Hz; 10 m/s2,9~200Hz; 15 m/s2,200~500Hz | ||
Storage temperature | −40~+70ºC |
1.6 Product Outline, Mounting Dimension, and Weight
V61−H−4T7.5G & V51−H−4T7.5G and below power class
V61−H−4T11G & V51−H−4T11G and above power class
Fig. 1−2 Product outline and mounting dimension
Product outline, mounting dimension, and weight
Voltage class | Inverter model | Outline and mounting dimension (mm) | Approximate weight (kg) | |||||||
W | H | D | W1 | H1 | D1 | T1 | Mounting hole diameter | |||
200V | V61−H−2T0.4G | 118 | 190 | 155 | 105 | 173 | 40.8 | 3 | 5.5 | 1.5 |
V61−H−2T0.75G | 175 | 60.5 | 4 | 2.2 | ||||||
V61−H−2T1.5G | 155 | 40.8 | 3 | 1.5 | ||||||
V61−H−2T2.2G | 175 | 60.5 | 4 | 2.2 | ||||||
400V | V61−H−4T0.75G/1.5L | 118 | 190 | 155 | 105 | 173 | 40.8 | 3 | 5.5 | 1.5 |
V61−H−4T1.5G/2.2L | 118 | 190 | 175 | 105 | 173 | 60.5 | 4 | 5.5 | 2.6 | |
V61−H−4T2.2G/3.7L | ||||||||||
V61−H−4T3.7G/5.5L | ||||||||||
V61−H−4T5.5G/7.5L | 155 | 249 | 185 | 136 | 232 | 69 | 8 | 5.5 | 4.5 | |
V61−H−4T7.5G/11L | ||||||||||
V61−H−4T11G/15L | 210 | 337 | 200 | 150 | 324 | 88 | 2 | 7 | 8.5 | |
V61−H−4T15G/18.5L | ||||||||||
V61−H−4T18.5G/22L | 289 | 440 | 220 | 200 | 425 | 88 | 2.5 | 7 | 17 | |
V61−H−4T22G/30L | ||||||||||
V61−H−4T30G/37L | ||||||||||
V61−H−4T37G/45L | 319 | 575 | 218 | 220 | 553 | 90.5 | 2.5 | 10 | 25 | |
V61−H−4T45G/55L | ||||||||||
V61−H−4T55G/75L | 404 | 615 | 255 | 270 | 590 | 86.5 | 3.0 | 10 | 35 | |
V61−H−4T75G/90L | ||||||||||
V61−H−4T90G V61−H−4T110L
| 465 | 745 | 325 | 343 | 715 | 151.5 | 3.0 | 12 | 55 | |
V61−H−4T110G V61−H−4T132L
| ||||||||||
V61−H−4T132G V61−H−4T160L
| 540 | 890 | 385 | 370 | 855 | 205.5 | 4.0 | 14 | 85 | |
V61−H−4T160G V61−H−4T185L
| ||||||||||
V61−H−4T185G V61−H−4T200L | ||||||||||
V61−H−4T200G V61−H−4T220L | ||||||||||
V61−H−4T220G V61−H−4T250L | 700 | 1010 | 385 | 520 | 977 | 210 | 4.0 | 14 | 125 | |
V61−H−4T250G V61−H−4T280L | ||||||||||
V61−H−4T280G V61−H−4T315L
| ||||||||||
V61−H−4T315G V61−H−4T355L
| 810 | 1358 | 425 | 520 | 1300 | 210 | 4.0 | 14 | 215 | |
V61−H−4T355G V61−H−4T400L
| ||||||||||
Voltage class | Inverter model | Outline and mounting dimension (mm) | Approximate weight (kg) | |||||||
W | H | D | W1 | H1 | D1 | T1 | Mounting hole diameter | |||
400V | V61−H−4T400G V61−H−4T450L | 810 | 1358 | 425 | 520 | 1300 | 210 | 4.0 | 14 | 215 |
V61−H−4T450G V61−H−4T500L | ||||||||||
V61−H−4T500G V61−H−4T560L |